Maintaining the electrical system 73
8. Adjust the straight sides of the seal so that they stick out a little, just
enough so that you can feel the seal when you run a finger across the
joint.
9. Cross-tighten the cover bolts evenly and gradually. The correct torque
for these bolts is 2 Nm (1.5 ft.-lbs.). At this torque, the seal will be
compressed by about one-third.
Adjusting power on 277 volt models
This procedure only applies to models factory wired for 277 V supply (see
the serial number label on the fixture). If the Exterior 600 model is factory
wired for another voltage, see “Adjusting power (on models other than 277
volts)” on page 71.
1. Make sure the Exterior 600 is isolated
from AC power and has cooled for at
least 20 minutes.
2. To open the fixture, remove the 10
Allen screws from the rear cover plate.
Carefully remove the plate and seal.
3. Locate the BROWN wire that connects
the mains filter to the transformer.
Move this wire to the transformer terminal labelled for the desired
setting, 230 or 277 V. Do not move the brown wire that leads to the
ballast.
4. To tap the ballast, move the single BROWN wire to terminal 7 for 60 Hz
operation, or to terminal 10 for 50 Hz operation.
5. Before closing, check the condition of the cover plate seal. Replace with
a new one (P/N 20600020) if the seal is torn, cracked or brittle.
Local AC Transformer Ballast
Frequency Voltage Setting Terminal Setting Terminal
50 Hz 218-241 V 230 V see label 230 V / 50 Hz 10
265-290 V 277 V see label
60 Hz 218-241 V 230 V see label 227 V / 60 Hz 7
265-290 V 277 V see label
Ballast
Tran s-
former
Fuse